GAB4-63 6KA breaking capacity mini circuit breaker

GAB4-63 6KA breaking capacity mini circuit breaker
Product Detailed
Related Categories:Circuit Breakers
1. 6KA high breaking capacity 2. CE certification 3. good quality and price

APPLICATION

GAB4-63 high-breaking capacity mini circuit breaker is mainly used for the protection against overload and short circuit under the alternating current 50Hz/60Hz,rated voltage 230V or 400V and with rated current 1 to 63A.It can also be used for unfrequent on-and-off switching electric equipment and lighting clrcuit in normal case.This circuit breaker is applied to industry, commerce,high-rise building,household and other similar installations.The product complies IEC 60898-1

Its charateristics are as follows:

1.Reliable contact mode indicator.

2.With double connecting methods,it can connect standard busbar and soft & hard wire.

3.Enclosure and some functional parts are all adopted with high fireresistant,hightemperature    resistant and shock proof plastic.

4.High current-limiting characteristic.

MAIN SPECIFICATIONS AND TECHNICAL PARAMETERS

1.According to rated current ln:1A,2A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A

2.According to mode of the instantaneous tripping current:B type(3~5)ln,C type(5~10)ln,

                                                                                    D type(10~20)ln;

3.According to the number of poles:1P,2P,3P,4P

4.Mechanical & electrical endurance:

Electrical endurance(times)Mechanical endurance(times)Operating frequency(times/hour)Rated current
4000100002401~32
40001000012040~63

5.Wiring:applicable for conducting wire<25mm

Rated current ln(A)Nominal cross sectional area of the conducting wire(mm)
1~6                      1
10                      1.5
1620                      2.5
25                      4
32                      6
4050                     10
63                     16

6.Rated short-circuit breaking capacity:

Rated currentPole numberRated voltage(V)Rated short-circuit breaking current(A)Power factor cosφ
1~63A1230/40060000.7
2,3,440060000.7

GAB4-63 6KA breaking capacity mini circuit breaker